SF6 GAS TEST


Testing Procedures

  • SF6 Dew Point Test.
  • SF6 Purity Test.
  • SF6 Leakage Test.
Download: SF6 Dew Point Test Format.
            SF6 Purity Test Format.

Equipment Required

  1. Dilo Multi Analyzer.
  2. Dilo Leakage Tester.
Picture
Dilo Multi Analyzer
Picture
Dilo Leakage Tester

Dew Point /Purity Test

  • Use Dilo Multi Analyzer for Testing.
  • Connect the fitting hose at GIS Compartment.
  • From Setting make Auto Pumping ON to return the gas back to the compartment.
  • From main screen press I to start the test.
  • Wait until the test finish 100%, then the kit will start pumping gas back to the compartment.
  • Press Metered Values to get the results.
  • Percentage% : SF6 Purity Percentage.
  • Dew Point: SF6 Dew Point Degree./ PPm.
  • PPm: Part Per Million.

Picture
SF6 Fitting Hose
Picture

SF6 Leakage Test

  • SF6 Leakage Test:
    • Make Raping for SF6 Compartment junctions.
    • Keep for 24 hours.
    • Make a small hole on the raping, then insert the sensor.
    • If there is any gas leakage the sensor will detect.
Powered by Create your own unique website with customizable templates.
  • Home
    • Site Map
    • About Substations
  • Formats
    • Auxiliary Relays
    • Equipments Formats
    • Protection Formats >
      • Energization Tests
    • Functional Test Format
  • Manuals
  • Software
  • Support
    • Testing & Commissioning
    • Test Procedures
    • Relays Calculations
    • Relays Configuration
    • Tutorials
    • References
    • Label Design
  • Blog
  • About Me