Analogue Meters Testing
Testing Procedures
Calibrate the meter at different values.
Download:
Meters Test Format
Equipment Required
Injection Kit (Freja).
Connection Cables (Banana Type).
FREJA 300
Connection Cables
Meter Calibration Test
Connection will be same as the shown figure.
Adjust meter pointer exactly at zero scale.
Sometimes we connect a series resistor to control injected current for small scale meters.
For Ammeters:
Inject AC current with different values (25%, 50%, 75% & 100% of full scale).
Calculate the meter error accuracy at each value.
For Voltmeters:
Inject AC Voltage with different values (25%, 50%, 75% & 100% of full scale).
Calculate the meter error accuracy at each value.
Connection Circuit