Voltage Transformer Testing
Testing Procedures
Insulation Resistance test.
Voltage Transformer Ratio & Polarity test.
Winding Resistance test.
Download:
VT Test Format
Equipment Required
CPC 100 for VT Ratio & Polarity test.
Insulation Resistance tester: Megger mit1020.
Multimeter.
Micro ohm meter: Drlo10
CPC 100
Insulation Tester
Multimeter
Micro ohm Meter
Insulation Resistance Test
Use Megger mit1020 to measure insulation resistance.
Insulation Resistance Tests to be done:
Primary
winding
- Ground (Apply 1kV for 1 minute)
Primary winding - Secondary
winding (Apply 500V for 1 minute)
Secondary winding - Secondary winding (Apply 500V for 1 minute)
Secondary - Ground (Apply 500V for 1 minute)
VT Ratio & Polarity Test
Use Omicron CPC100 to test VT ratio & polarity.
Connection on CPC100 will be same as the shown figure.
Repeat the test for the other phases and the other secondary cores.
Winding Resistance Test
Use multimeter to measure the primary winding resistance (Normally in k ohm).
Use the micro ohm meter to measure the secondary winding resistance ( Normally in m ohm).
Home
Site Map
About Substations
Formats
Auxiliary Relays
Equipments Formats
Protection Formats
>
Energization Tests
Functional Test Format
Manuals
Software
Support
Testing & Commissioning
Test Procedures
Relays Calculations
Relays Configuration
Tutorials
References
Label Design
Blog
About Me